MIDC/Data Quality Statements
Total Records: 48, displaying 26-48
[Prev Records]
R#SiteSerial NumberMeasurementStart DateStart TimeEnd DateEnd TimeData Quality Statement
26BMS953001Direct CUVB208/13/201200:00:0008/15/201215:04:00There is a signal problem with the Direct CUVB2, which is causing the signal to be lower than it should be and a tad noisy. Signal is also negative at night. Channel was shorted on 8/15/2012 and the problem appeared to be between patch panel and data logger. However problem fixed itself before patch panel could be opened.
27BMS953001Direct CUVB207/20/201200:00:0007/23/201208:11:00There is a signal problem with the Direct CUVB2, which is causing the signal to be lower than it should be and a tad noisy. Signal is also negative at night. J-box connector was re-seated which seemed to fix the problem.
28BMSDirect CUVB207/06/201219:35:0007/09/201210:18:00A GFCI on the North tracker post was tripped due to thunderstorms. Data from the following instruments are bogus due to not having power during this time: CUVA2, CUVB2, TWC, PGS-100, POM-01.
29BMSDirect CUVB205/26/201206:15:0005/26/201207:12:00Due to a planned power outage for SRRL electrical work, the following BMS instruments were down: TSP-1, TSP-700, UVSAT, UVSBT, CUVA1, CUVA2, CUVB1, CUVB2, UVB-1, 501A, MS210W, SPN1, PGS-100, POM-01, TWC.
30BMS953001Direct CUVB201/03/201209:00:0001/18/201209:09:00There is a signal problem with the Direct CUVB2, which is causing the signal to be lower than it should be and negative at night or overcast conditions. J-box connector was re-seated which seemed to fix the problem.
31BMSDirect CUVB211/12/201111:59:0011/12/201113:26:00Due to an undervoltage followed by a power outage at 13:12, the following BMS instruments may be reading bogus or invalid data: TSP-1, TSP-700, UVSAT, UVSBT, CUVA1, CUVA2, CUVB1, CUVB2, UVB-1, 501A, MS210W, SPN1, TWC.
32BMSDirect CUVB209/08/201105:56:0009/08/201109:19:00Due to a planned power outage for SRRL construction activities, the following BMS instruments were down: TSP-1, TSP-700, UVSAT, UVSBT, CUVA1, CUVA2, CUVB1, CUVB2, UVB-1, 501A, MS210W, SPN1, PGS-100, POM-01, TWC.
33BMSDirect CUVB207/12/201122:57:0007/13/201107:40:00Due to a tripped GFCI outlet at SRRL the following instruments were without power during this time: TWC & POM-01 Photometers, Direct CUVA2 & CUVB2, and the PGS100. The readings are either zero or bogus and should not be used. GFCI was tripped due to Eppley venitlators which were water logged by thunderstorm.
34BMSDirect CUVB206/14/201113:01:0006/14/201113:14:00Due to a planned power outage for SRRL construction activities, the following BMS instruments were down: TSP-1, TSP-700, UVSAT, UVSBT, CUVA1, CUVA2, CUVB1, CUVB2, UVB-1, 501A, MS210W, SPN1, TSI-880, PGS-100, POM-01, EFM-100.
35BMSDirect CUVB205/25/201105:19:0005/26/201112:16:00Due to a planned power outage for SRRL construction activities, the following BMS instruments were down: TSP-1, TSP-700, UVSAT, UVSBT, CUVA1, CUVA2, CUVB1, CUVB2, UVB-1, 501A, MS210W, SPN1, TSI-880, PGS-100, POM-01, EFM-100.
36BMSDirect CUVB205/17/201114:20:0005/17/201114:48:00Due to a planned power outage for SRRL construction activities, the following BMS instruments were down: TSP-1, TSP-700, UVSAT, UVSBT, CUVA1, CUVA2, CUVB1, CUVB2, UVB-1, 501A, MS210W, SPN1, TSI-880, PGS-100, POM-01, EFM-100.
37BMSDirect CUVB205/07/201105:55:0005/09/201107:58:00There was a planned power outage for SRRL construction activities that started at 5:18 MST. Unfortunately, the backup generator provided to SRRL was providing bad power to the UPS powering the Sci-Tec trackers, therefore the UPS failed at 5:55 MST. Unfortunately, when normal AC power was restored at 11:45 MST, the Sci-Tec trackers had lost all their configuration due to UPS cycling on and off during the outage, therefore were not tracking. The tracker settings were restored on May 9 at 7:58 MST. The following BMS instruments were not pointing at the sun during this time: Direct CH1, NIP #2, NIP #1, LI-201, NIP RG780, CUVA2, CUVB2, TWC; and the following instruments were un-shaded: Diffuse 8-48, PSP, CM22, CUV4, PIR, CG4
38BMSDirect CUVB205/07/201105:18:0005/07/201111:45:00Due to a planned power outage for SRRL construction activities, the following BMS instruments were down: TSP-1, TSP-700, UVSAT, UVSBT, CUVA1, CUVA2, CUVB1, CUVB2, UVB-1, 501A, MS210W, SPN1, TSI-880, PGS-100, POM-01, EFM-100.
39BMSDirect CUVB204/15/201106:11:0004/15/201106:50:00Due to a planned power outage for SRRL construction activities, the following BMS instruments were down: TSP-1, TSP-700, UVSAT, UVSBT, CUVA1, CUVA2, CUVB1, CUVB2, UVB-1, 501A, MS210W, SPN1, TSI-880, PGS-100, POM-01, EFM-100.
40BMSDirect CUVB207/04/201018:10:0007/06/201007:30:00Due to several tripped GFCI outlets at SRRL the following instruments were without power from July 4 @ 18:10 to July 6 @ 7:30 MST: Global CUVA1, CUVB1, MS210W, 501A and Direct CUVA2, CUVB2, PGS100. The readings are either zero or bogus and should not be used.
41BMS953001Direct CUVB206/11/201014:38:0006/14/201008:01:00The Kipp & Zonen Direct CUVA2 and CUVB2 were without power during this time, most likely due to tripped GFI caused by hail storm. Measured signal is bogus.
42BMSDirect CUVB205/27/201018:00:0005/28/201012:15:00Due to improper mounting of the replacement CH1 s/n 080033 the Sci-tec tracker was not tracking properly due to collision with the CH1 against tracker. The following BMS instruments were not pointing at the sun: Direct CH1, NIP2, CUVA2, & CUVB2 and the following instruments were unshaded: 8-48, PSP, PIR.
43BMSDirect CUVB212/09/200910:52:0012/09/200914:22:00Due to a power outage (and bad power) at NREL, the following BMS instruments were down: TSP-1, TSP-700, UVSAT, UVSBT, CUVA1, CUVA2, CUVB1, CUVB2, UVB-1, 501A, MS210, SPN1, Snow Depth, TSI-880, POM-01.
44BMSDirect CUVB211/15/200807:45:0011/15/200814:29:00Due to a planned power outage at SRRL, the following BMS instruments were down: TSP-1, TSP-700, UVSAT, UVSBT, CUVA1, CUVA2, CUVB1, CUVB2, UVB-1, 501A, MS210, SPN1, Snow Depth, TSI-880, SkyCam.
45BMS953001Direct CUVB205/25/200610:50:0005/25/200611:26:00Sun Follower III tracker was down due to power shutdown for installation of new SRRL equipment lift. The following instruments were NOT pointing at the SUN: NIP #1, NIP RG780, CUVB2, LI-201, TWC (500nm).
46BMS953001Direct CUVB211/05/200506:37:0011/07/200508:10:00Sun Follower III tracker was down due to a power outage on 11/4/2005 at 23:14 MST. The following instruments were NOT pointing at the SUN: NIP #1, NIP RG780, CUVB2, LI-201.
47BMS953001Direct CUVB207/23/200510:16:0007/24/200509:01:00Sun Follower III tracker was down due to a scheduled NREL power outage on 7/23/2005 at 5:33 MST. The following instruments were NOT pointing at the SUN: NIP #1, NIP RG780, CUVB2, LI-201.
48BMS953001Direct CUVB207/16/200500:00:0007/18/200507:46:00The Sun Follower III tracker was hung up on cables, due to a research NIP removal that occured earlier in the week. This instrument was not pointing at the sun during this time.