R#SiteSerial NumberMeasurementStart DateStart TimeEnd DateEnd TimeData Quality Statement
1BMSRoof Temp and RH04/06/199909:18:0004/07/199909:45:00The Roof Temperature sensor was mistakenly disconnected during this time period.
2BMSRoof Temp and RH01/01/180010/28/199912:23:00The Vaisala relative humidity and temperature (roof) probe, model HMP-35C used in the SRRL Baseline Measurement System has drifted significantly out of calibration (start date is unknown). A new probe will be installed soon. A comparison of the old and new sensors was done from October 10-13, 1999, a plot showing the output vs time and a correlation between the two has been produced. The user can correct the data (during this time frame) using the equation: RH (correct) = 0.83244 * RH(BMS) - 3.4232